规格书
Features | |
---|---|
Electrical measurement | Current (A); power(kW); voltage(V); energy(KWH) etc. |
Metering per PDU | Yes |
Metering per outlet | No(Each socket can be set with alias management) |
Metering accuracy | +/- 1% billing grade |
Outlet switching | No |
Input Switching | Access to flooding, smoke, etc. |
Output Switching | Access control and other equipment |
Display | LCD Display (Display active current, active voltage,active power) |
Network | 10/100 Mbit/s Auto-sensing |
Device login mode | Web,Login through username and password,Maximum 16 accounts can be set up |
Supported network protocols | SSH、WiFi、TCP/IP、SNMP V1 V2 |
USB Port | 3 USB2.0 ports for timing modules, etc. |
Alarm settings | Yes(Current, voltage, power upper and lower threshold alarms) |
Alarm mode | Email,screen flashing alarm |
information storage | Yes(Data retention time of about 12 months for current, voltage, power, kWh, etc.) |
log list | Yes |
Input | |
---|---|
Input plug | IEC 60309 16A 5-pin |
Input cable | 3m 3C 5*6mm² |
Rated current | 32A |
Rated voltage | 250 VAC |
Phases | single phases |
Frequency | 50/60 Hz |
maximum power | 8000w |
Output | |
---|---|
Sockets | 4-ports IEC C19 anti-shedding (green) + 20-digit IEC C13 anti-shedding (10 red + 10 blue) |
Protection and Monitoring Function | Hot-swappable lightning protection |
Control and Indicator Function | Hot Swap Indicator Light |
Physical | |
---|---|
Dimensions (L*W*H) | 1593.8x52x62 mm |
Profile | aluminium alloy |
Shell color | Black, Yellow (multiple colors available) |
Mounting | Tool free installation or universal installation accessories |
Plastic Materials | PC/ABS Flame retardant V0 ,Glow wire resistant 850°C |
Environmental | |
---|---|
Maximum elevation | 0-3,000m |
Temperature (operating / storage) | -5-60°C/-15-65℃ |
Relative humidity | 5-95% RH. Non condensing |
Compliance | |
---|---|
Certification | ISO9001 |